上海頤品自動化科技有限公司
產地 | 進口 | 加工定制 | 否 |
---|
Hawke非鎧接管型防爆格蘭(501/414系列)
Hawke防爆格蘭代理商:上海頤品自動化科技有限公司
Hazardous Area Cable Glands from Hawke
Hazardous Area Cable Glands-ATEX IECEX,Exe,Exd Group II
Hawke防爆格蘭代理商:上海頤品自動化科技有限公司(4008552521)
關鍵詞:Hawke防爆格蘭,Hawke防爆變徑,Hawke防爆堵頭,Hawke防爆呼吸閥,Hawke防爆接線盒,Hawke防爆控制箱
Hawke防爆格蘭等產品規格書及相關證書-請咨詢上海頤品自動化科技有限公司
Hawke 501/414 cable glands are suitable for use with non-armoured elastomer and plastic insulated cables installed in conduit for both outdoor and indoor use.
Hawke 501/414 cable glands are dual certified Exd and Exe and suitable for installation in Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC, 3.0-65.3mm outside cable diameters.
When used in increased safety applications the Hawke cable gland can be used to terminate braided cables where the braid and the cable outer sheath enter into the electrical enclosure or junction box.
? Exdb IIC Gb, Exe IIC Gb, Extb IIIC, Db Non-aromoured Cables ATEX & IECEx Cable Gland.
Hawke 501/414 cable gland is suitable for cable termination and installation in Zone 1 (21), Zone 2 (22) and Division 2 hazardous areas.
Flameproof Exdb
Increased Safety Exeb
Dust Extb
Dual Certified Cable Gland For Hazardous Areas ATEX – IECEx
Hazardous Area Cable Gland Classification – Exdb IIC Gb, Exeb IIC Gb, Extb IIIC Db
Certificate No’s – baseefa06ATEX0056X and IECEx BAS 06.0013X
Cable Gland Zone Location – Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC
Construction and Test Standards – IEC/EN 60079-0, IEC/EN 60079-1, IEC/EN 60079-7 and IEC/EN 60079-31
Ingress Protection – IP66, IP67 and IP 68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X
Deluge Protection – DTS01
Operating Temperature Range -60°C to +100°C
Hawke Size Ref. | Male Entry Thread Size | Female Entry Thread Size | Cable Acceptance Details | ‘G’ Compressed Length | Hexagon Dimensions | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Outer Sheath ‘B’ | ||||||||||||
Metric | NPT * | Metric | NPT # | Standard Seal | Alternative (S) Seal | Across Flats | Across Corners | |||||
Standard | Option | Min. | Max. | Min. | Max. | |||||||
Os | M20 ? | ?" | – | M20 | – | 3.0 | 8.0 | – | – | 54.5 | 24.0 | 26.5 |
O | M20 ? | ?" | – | M20 | – | 6.5 | 11.9 | – | – | 54.5 | 24.0 | 26.5 |
A | M20 | ?" | ?" | M20 | – | 10.0 | 14.3 | 9.0 | 13.4 | 56.4 | 30.0 | 32.5 |
B | M25 | 1″ | ?" | M25 | – | 13.0 | 20.2 | 9.5 | 15.4 | 48.2 | 36.0 | 39.5 |
C | M32 | 1?" | 1″ | M32 | – | 19.0 | 26.5 | 15.5 | 21.2 | 61.6 | 46.0 | 50.5 |
C2 | M40 | 1?" | 1?" | M40 | – | 25.0 | 32.5 | 22.0 | 28.0 | 64.6 | 55.0 | 60.6 |
D | M50 | 2″ | 1?" | M50 | – | 31.5 | 44.4/42.3 ? | 27.5 | 34.8 | 83.2 | 65.0 | 70.8 |
E | M63 | 2?" | 2″ | M63 | – | 42.5 | 56.3/54.3 ? | 39.0 | 46.5 | 83.2 | 80.0 | 88.0 |
F | M75 | 3″ | 2?" | M75 | – | 54.5 | 68.2/65.3 ? | 49.5 | 58.3 | 86.4 | 95.0 | 104.0 |
Cembre cable lugs available to crimp and terminate cable conductors to ensure complete termination of cable.
Hawke 501/414 cable glands are manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminium. Brass NPT entries are nickel plated as standard.
Pull sufficient length ‘I’ of cable through conduit/cable gland to suit equipment. Screw backnut (1) onto pre-threaded conduit/cable gland and tighten with spanner/wrench.
Pass the cable through the entry (5) and seal which may have previously been fitted into the equipment.
Locate the running coupler (2) onto the entry (5) and tighten using a wrench/spanner until resistance is felt between the seal and cable, then turn the running coupler through a further half to one full turn to complete the inner seal, ensuring that entry (5) is prevented from turning and backnut (1) remains tight on the conduit. This procedure compresses the seal into contact with the cable outer sheath.
Click Hawke Cable Glands to view the complete range of hazardous area glands certified according to ATEX & IECEx for Zone 1 / Zone 2.
Flameproof Exdb and Increased Safety Exeb (Dust Extb) Dual Certified glands from Hawke include – for further information review the product pages or contact us to discuss your cable gland requirements.
501/421 Cable Gland Unarmoured – outer cable sheath cable sealing
501/423 Cable Gland Unarmoured – flameproof seal to inner/outer cable sheath with IP seal on the outer sheath
501/453 Universal Cable Gland Wire Armoured Baided Steel Tape Armoured – indoor/outdoor hazardous areas
ICG 623 Barrier Gland Unarmoured – Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC hazardous areas
ICG 653 Barrier Gland Armoured – Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC hazardous areas
Hazardous Area Cable Glands-ATEX IECEX,Exe,Exd Group II
Hawke防爆格蘭代理商:上海頤品自動化科技有限公司(4008552521)
關鍵詞:Hawke防爆格蘭,Hawke防爆變徑,Hawke防爆堵頭,Hawke防爆呼吸閥,Hawke防爆接線盒,Hawke防爆控制箱
Hawke防爆格蘭等產品規格書及相關證書-請咨詢上海頤品自動化科技有限公司
您感興趣的產品PRODUCTS YOU ARE INTERESTED IN
儀表網 設計制作,未經允許翻錄必究 .? ? ?
請輸入賬號
請輸入密碼
請輸驗證碼
請輸入你感興趣的產品
請簡單描述您的需求
請選擇省份